Hontai Machinery and equipment (HK) Co. ltd
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Insulation resistance phase electric protection relay 110V(JT(DT)-1-1-110, DT-1/200, JT-1-2-57.7, JT-1-2) )
Model :
JT-1 series phase relay(JT(DT)-1-1-110)
JT-1 series phase relay(JT-1-2-57.7)
JT-1 Sync check relay(JT-1-2)
JT-1 series phase relay(DT-1/200)
JT-1 series phase relay is used in outo-reclosing circuit of two port power supply circuit, to check the vector difference betwiin the vector quantity of the teo port circuit.
1 Setting value range
Only phase:5°175°
Voltage vector:110V
2 Contact capacity 250VAC COSφ=1.0 5A
Closing brake: 250VDC 5A
Triping brake 250VDC τ=5mS 50W
3 Contact life Electrical life: More than 105 times; Mechanical life: More than 106 times.
4 Medium intensity Relay’s every electric terminals are connected together. And ia can endure a 2000V and 50Hz AC voltage (virtual value) to the non-electrification metallic outside part or shell.There is no inxulated breakdown or flashover phenominon.
5 Insulation resistance Relay’s every electric terminals are connected together. To the non-electrification metallic outside part or shell, its insulated resistance is less than 300MΩ measured by tramegger with opening voltage is 500V.
6 Working condtion Temperature -10+50, relative humidity≤90%, altitude≤2000m